Incorrect parameter settings: The recovery voltage threshold on older models may be configured too low for current grid standards. During off-peak periods, the grid voltage rises slightly, and it may exceed the protector's recovery value, preventing it from reclosing or causing it to trip repeatedly.
Why Does My Over-under Voltage Protector Trip Repeatedly?

Frequent tripping of the resettable overvoltage and undervoltage protector is commonly caused by sensed voltage anomalies, internal device faults, or issues within the household wiring system.
Common Causes of Tripping
1. Grid voltage fluctuations
This is the most common external cause. Electrical load changes can cause voltage fluctuations—e.g., high evening grid demand often raises voltage, triggering protection.
2. Protector malfunction or improper settings
-
-
Product quality or installation issues: The use of substandard protectors or improperly tightened terminal screws during installation can result in poor electrical contact. This may lead to frequent tripping or even damage to the device.
- Lack of overload and short-circuit protection: The resettable overvoltage and underVoltage Protector itself does not provide overload and short-circuit protection. If no circuit breaker is connected in series upstream of the protector, a short circuit or severe overload in the line may result in a large current that can directly damage the protector.
3. Household wiring or appliance issues
-
-
Effects of high-power appliances: When multiple high-power appliances, such as air conditioners, are started simultaneously, the inrush current can be extremely large. This may cause a transient voltage drop, which can activate the protection.
How to Diagnose the Issues?
-
-
Check the indicator light status:
-
Rapid red flashing indicates overvoltage.
-
Slow red flashing indicates undervoltage.
-
Red illumination indicates phase loss or internal fault.
-
- Wiring inspection: Only perform inspections if you are qualified. Check that all terminal screws are properly tightened and verify that the live wire and neutral wire are connected to the correct terminals. Confirm that a MCB is installed in series upstream of the protector.
-
